WOODWARD 2301A Load Distribution and Speed Controller
Source: | Author:kongjiang | Published time: 2026-05-29 | 14 Views | 🔊 Click to read aloud ❚❚ | Share:
2301A Load Distribution and Speed Controller

app; application

2301A load distribution and speed controller is mainly designed for electronic power generation systems that need multi-unit load distribution. 2301A controller can be used with diesel engine, gas engine, gasoline engine, steam turbine or gas turbine. Can be applied to control:

It can be used in situations where differential/synchronous speed regulation is needed.

Forward or reverse action mode

Single or sequential actuator

Acceleration or deceleration slope

Wide speed range

describe

Auto-adjustable starting fuel limit adjusts the maximum fuel position when starting the machine. Help reduce pollution and engine wear. Each 2301A controller has its own integrated load sensor. Most modules can output 0-200mA control signals, and can cooperate with Woodward EG, EGB, PB, TM and 2301 actuators. 0–20 Ma output signal can be used in special occasions. The output number is proportional to the fuel.

Set according to speed/load. The position feedback signal of the actuator is not needed. 2301A controller is compatible with Woodward SPM-A synchronizer and automatic generator load control. Process input/output control and automatic power transfer and load control.

Reliable control:

Simple regulator

2310A LSSC controller can work in harsh environment. The built-in protective device can prevent electromagnetic interference/high frequency harmonic interference (EMI/RFI), moisture, dust and vibration.

2301A controls a printed circuit board. All potentiometers can be operated from the front of the chassis. The speed range can be set by the internal dip switch. Open the housing cover to operate. The rotational speed can be set according to the frequency of the speed sensor. The external speed regulator can be connected to remote control and manual operation. The deceleration slope is adjustable.

General characteristics

Power supply 90–150VDC or 85–132VAC high-voltage mode and 20–40VDC low-voltage mode internal power consumption < 15 W.

Input—

Load sensing 90–240VAC345–66HZ3Current sensor input.

Speed sensor input resistance 100–300

Speed sensor electromagnetic 1.0VAC-30VAC

Speed adjustment 0–100 for 0 to 10% speed change

Speed setting terminals 23-24 jumper, internal 100 adjustable potentiometer allows external 0-10% speed adjustment.

Idle speed selection external switch, open terminals 19 to 16.

Adjust the external switch differentially and open terminals 14 to 16.

Adjust ±5 Vdc synchronously and use Woodward SPM-A synchronizer to adjust the speed.

Load distribution 0–6 VDC