RTU560 product line
Communication module of the RTU560 with 32 bit
CPU
• 6x serial communication interface (RS-232 or
RS-485) for remote communication
• 2x Ethernet interface (10/100BaseT)
• 1x USB port
• 1x serial peripheral bus
• battery buffered real time clock
Application
The 560CMR02 communication unit is one of the CMU
modules of the RTU560 product line.
The essential tasks are:
• Managing and controlling of the I/O modules via the
interface to the serial I/O bus.
• Reading Process events from the input modules.
• Send commands to the output modules.
• Communicating with control systems and local HMI
systems via the serial interface (RS232) and the
Ethernet 10/100BaseT interfaces.
• Communication with Sub-RTU’s, IED’s or multimeter
devices via the interfaces (RS485) and the Ethernet
interfaces.
• Managing the time base for the RTU560 product line
station and synchronizing the I/O modules.
• Handling the dialog between RTU560 product line and
Web-Browser via the LAN interfaces.
Within the RTU560 racks the board occupies two slots.
The communication unit is able to handle Ethernet- and
UART-character based communication protocols.
The unit has a battery buffered real time clock (RTC).
The unit is available in 2 versions:
• R0001: with standard cyber security functions
• R0002: with security chip for advanced cyber security
functions
Characteristics
On the applied ARM cortex A8 controller AM3352 a real
time operating system is implemented. The 560CMR02
is responsible for the interface management, the event
handling, the time base and the internal data base. The
controller acts as master for the SPB I/O bus (serial peripheral bus). RTU560 synchronizes itself to the time
references supplied by 560RTC0x. The time information
of the 560RTC0x is provided to the 560CMR02 on the
backplane of the sub-rack.
System relevant configuration files are stored in the non
volatile flash memory card (removable SD-card™) in order
to guarantee a valid system configuration after Power on
Reset (PoR).
A battery buffered RTC is used to keep an exact time
during power off state.
The communication unit provides the following interfaces:
• Communication Port 1 ... 6 (CP1 ... CP6): serial
interfaces according RS232C or RS485 with RJ45
connectors. CP1 and CP2 can be configured
independant as SPB I/O bus interface to the front.
• Ethernet interface 1 and 2 (E1 & E2): 10/100BaseT
with RJ45 connector.
• USB 2.0 device interface for diagnosis and
maintenance purposes.
• The SPB I/O bus is directly connected to the
backplane connector.
Same series model
ABB Hitachi 560CVD03R0041
ABB Hitachi 560CVD03R0051
ABB Hitachi SCADA 560CMU05
ABB SCADA 560PSU01
ABB 560PSR00
ABB 560CMR02 R0001
ABB 560BOR01 R0002
ABB 560BIR01 R0002
ABB LDMUI-01 61320946C
ABB XVC724BE102 3BHE009017R0102
ABB UFC921A 3BHE024856P201
ABB UAC389 HIEE410506P104
ABB BN5930
ABB NTAC-02 58967441E
ABB CT-APS.22 1SVR630180R3300
ABB SZ4127.000
ABB GRBTU-01 3BSE013175R1
ABB RM302024
ABB RM602024
ABB LT2005-S/SP19
ABB B09261
ABB KTO 011 KTO011
ABB KTS 011 KTS011
ABB TNR 25590 TNR25590
ABB "3BHE006373R0101 XVC769 AE101
HIEE410506P104"
ABB SCYC51204 63912476
ABB SCYC51204 63912476C
ABB SCYC51213 63911607C
ABB FPX86-9364-A