Easy Gen-3400XT-P1/3500XT-P1/3500XT-P1-LT series generator set control system provides comprehensive function and status indication. Its HMI is consistent with the function sequence and structure of ToolKit, but full access to all parameters and settings is limited to ToolKit. LT model is equipped with a heatable display screen, which automatically starts heating when the ambient temperature is lower than-20 C, and the power consumption increases by 7.5W during heating. HMI buttons can be locked or unlocked through LogicsManager. The front panel contains soft key groups such as display screen, mode, operation, navigation, home page and alarm. The system status is displayed by communication and operation indicator lights. The communication status indicates the data reception of CAN port, and the operation status reflects the equipment readiness and alarm status. The control system supports a variety of application modes, including circuit breaker-free control, generator circuit breaker control, main circuit breaker control and combined control modes, and each mode provides engine/generator parameter measurement, start-stop and protection functions. The application modes include None, GCB open, GCB, GCB/MCB, GCB/GGB, GCB/GGB/MCB, GCB/LS5, GCB/L-MCB, GCB/GGB/L-MCB and GCB/L-GGB/L-MCB, and some modes support automatic power failure operation. The system provides four operation modes: automatic, manual, test and shutdown, and the plastic shell version can be selected by the front panel button.

easYgen-3400XT-P1/3500XT-P1/3500XT-P1-LT | Genset Control

System Overview

Display And Status Indicators

HMI and ToolKit are aligned for the same sequence and structure of functions and parame ters.

Restrictions Full access to all parameters and settings with ToolKit only!

Low ambient temperature (LT) .... easYgen-3x00XT-P1-LT - the special version of the plastic housing device with HMI/display - is equipped with a heatable display. Heater is automatically switched ON when ambient temperature drops below -20 °C and the result [86.34 LM: Enable heater] (11972) of LM [7799 Enable front foil heater] is TRUE. Even if the device has no front foil heater because it is no ... LT variant, both the LogicsManager and the parameter are available but without function! During heating period the power consumption is increased by 7.5 W.

WARNING! 

 HMI buttons can be locked! HMI buttons can be locked/unlocked with the LogicsManager LM 12978 Ä p. 139/Ä p. 908 [Lock keypad]. Check/use with Logical Command Variable 86.30 (11924).



 Front Panel, Overview of Functional Groups of easYgen-3000XT with plastic housing

A Softbutton Group "Display" B Button Group "MODE" C Softbutton Group "Operation" D Softbutton Group "Navigation" E "Home" (screen) button F Group "ALARMS" (sign and button) G LCD Display (Screen) The softbutton groups A, C, and D provide the following functions via context-sensitive softkeys: A "Display"- Change the method of voltage and power calcu lations displayed. C "Operation"- Used to perform manual operation of the genset and the breakers (Single Line Diagram). Sometimes used for settings' input. D "Navigation"- Navigation between system and configuration screens, and alarm list.

System Overview

n “Communication” for visualizing communication state:

– Off: no data received by any CAN port

– Toggling green/off: any data is received by any CAN port

– Red: missing member alarm is active

– Toggling red/green: missing member is active and data received by any CAN port n “Operation” for device state indication:

– Off: the unit is not ready for operation (depending on LogicsManager "Ready for operation)– Green: the unit is ready for operation and no alarm is active or latched– Toggling green/red: the unit is ready for operation and a warning alarm in the system is active or latched– Red: the unit is ready for operation and a shutdown alarm in the system is active or latched.– Green blinking fast (about 6 times per second) and red is permanently off: Internal copy process after flashing a soft ware update is still running or "Load default settings" is initi ated

Application Modes Overview

The genset control provides the following basic functions via the application modes listed below.

None No breaker control. This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop

GCB open GCB control (open) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n Mains failure detection with mains decoupling (GCB)


GCB GCB control (open/close) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n GCB operation (relay output to close GCB) n Mains failure detection with mains decoupling (GCB)


GCB/MCB GCB/MCB control (open/close) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n GCB operation (relay output to close GCB) n MCB operation (relay outputs to open and close MCB) n Mains failure detection with mains decoupling (GCB and/or MCB) n Auto mains failure operation (AMF)

GCB/GGB GCB/GGB control (open/close) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n GCB operation (relay output to close GCB) n GGB operation (relay output to open and close the GGB) n Mains failure detection with mains decoupling (GCB)


GCB/GGB/MCB GCB/GGB/MCB control (open/close) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n GCB operation (relay output to close GCB) n GGB operation (relay output to open and close the GGB) n MCB operation (relay outputs to open and close the MCB) n Mains failure detection with mains decoupling (GCB/MCB) n Auto mains failure operation (AMF)


GCB/LS5 GCB/LS5 control (open/close) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n GCB operation (relay output to close GCB) n Connection to LS-5 system, LS5 runs as independent unit (Mode “LS5”) n Auto mains failure operation (AMF) guided by LS-5 system


GCB/L-MCB GCB/L-MCB control (open/close) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n GCB operation (relay output to close GCB) n MCB operation via LS-5, LS-5 runs as slave unit (Mode “L-MCB”) n Mains failure detection with mains decoupling via GLS or LS-5 (MCB) n Auto mains failure operation (AMF)


GCB/GGB/L-MCB GCB/GGB/L-MCB control (open/close) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n GCB operation (relay output to close GCB) n GGB operation (relay output to open and close the GGB) n MCB operation via LS-5, LS-5 runs as slave unit (Mode “L-MCB”) n Mains failure detection with mains decoupling via GLS or LS-5 (MCB) n Auto mains failure operation (AMF)


GCB/GGB/L-MCB GCB/GGB/L-MCB control (open/close) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n GCB operation (relay output to close GCB) n GGB operation (relay output to open and close the GGB) n MCB operation via LS-5, LS-5 runs as slave unit (Mode “L-MCB”) n Mains failure detection with mains decoupling via GLS or LS-5 (MCB) n Auto mains failure operation (AMF)


GCB/L-GGB/L-MCB GCB/L-GGB/L-MCB control (open/close) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n GCB operation (relay output to close GCB) n GGB operation via LS-5, LS-5 runs as slave unit (Mode “L-GGB”) n MCB operation via LS-5, LS-5 runs as slave unit (Mode “L-MCB”) n Mains failure detection with mains decoupling via GLS or LS-5 (MCB) n Auto mains failure operation (AMF)


Operation Modes

The easYgen-3000XT offers four operation modes:

n AUTO n MANUAL (MAN) 

n TEST n STOP 

n ... and an internal (non) operating phase during starting the device itself

The plastic housing (HMI) version of the easYgen-3000XT enables to select an operation mode by pressing the according button at the front panel - if current settings allow this function.