easYgen-3400XT-P1/3500XT-P1/3500XT-P1-LT | Genset Control
System Overview
Display And Status Indicators
HMI and ToolKit are aligned for the same
sequence and structure of functions and parame
ters.
Restrictions Full access to all parameters and settings with ToolKit only!
Low ambient temperature (LT) .... easYgen-3x00XT-P1-LT - the special version of the plastic housing device with HMI/display - is equipped with a heatable display. Heater is automatically switched ON when ambient temperature drops below -20 °C and the result [86.34 LM: Enable heater] (11972) of LM [7799 Enable front foil heater] is TRUE. Even if the device has no front foil heater because it is no ... LT variant, both the LogicsManager and the parameter are available but without function! During heating period the power consumption is increased by 7.5 W.
WARNING!
HMI buttons can be locked! HMI buttons can be locked/unlocked with the LogicsManager LM 12978 Ä p. 139/Ä p. 908 [Lock keypad]. Check/use with Logical Command Variable 86.30 (11924).

Front Panel, Overview of Functional Groups of easYgen-3000XT with plastic housing
A Softbutton Group "Display" B Button Group "MODE" C Softbutton Group "Operation" D Softbutton Group "Navigation" E "Home" (screen) button F Group "ALARMS" (sign and button) G LCD Display (Screen) The softbutton groups A, C, and D provide the following functions via context-sensitive softkeys: A "Display"- Change the method of voltage and power calcu lations displayed. C "Operation"- Used to perform manual operation of the genset and the breakers (Single Line Diagram). Sometimes used for settings' input. D "Navigation"- Navigation between system and configuration screens, and alarm list.
System Overview
n “Communication” for visualizing communication state:
– Off: no data received by any CAN port
– Toggling green/off: any data is received by any CAN port
– Red: missing member alarm is active
– Toggling red/green: missing member is active and data received by any CAN port n “Operation” for device state indication:
– Off: the unit is not ready for operation (depending on
LogicsManager "Ready for operation)– Green: the unit is ready for operation and no alarm is active
or latched– Toggling green/red: the unit is ready for operation and a
warning alarm in the system is active or latched– Red: the unit is ready for operation and a shutdown alarm
in the system is active or latched.– Green blinking fast (about 6 times per second) and red is
permanently off: Internal copy process after flashing a soft
ware update is still running or "Load default settings" is initi
ated
Application Modes Overview
The genset control provides the following basic functions via the
application modes listed below.
None No breaker control. This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop
GCB open GCB control (open) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n Mains failure detection with mains decoupling (GCB)
GCB GCB control (open/close) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n GCB operation (relay output to close GCB) n Mains failure detection with mains decoupling (GCB)
GCB/MCB GCB/MCB control (open/close) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n GCB operation (relay output to close GCB) n MCB operation (relay outputs to open and close MCB) n Mains failure detection with mains decoupling (GCB and/or MCB) n Auto mains failure operation (AMF)
GCB/GGB GCB/GGB control (open/close) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n GCB operation (relay output to close GCB) n GGB operation (relay output to open and close the GGB) n Mains failure detection with mains decoupling (GCB)
GCB/GGB/MCB GCB/GGB/MCB control (open/close) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n GCB operation (relay output to close GCB) n GGB operation (relay output to open and close the GGB) n MCB operation (relay outputs to open and close the MCB) n Mains failure detection with mains decoupling (GCB/MCB) n Auto mains failure operation (AMF)
GCB/LS5 GCB/LS5 control (open/close) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n GCB operation (relay output to close GCB) n Connection to LS-5 system, LS5 runs as independent unit (Mode “LS5”) n Auto mains failure operation (AMF) guided by LS-5 system
GCB/L-MCB GCB/L-MCB control (open/close) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n GCB operation (relay output to close GCB) n MCB operation via LS-5, LS-5 runs as slave unit (Mode “L-MCB”) n Mains failure detection with mains decoupling via GLS or LS-5 (MCB) n Auto mains failure operation (AMF)
GCB/GGB/L-MCB GCB/GGB/L-MCB control (open/close) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n GCB operation (relay output to close GCB) n GGB operation (relay output to open and close the GGB) n MCB operation via LS-5, LS-5 runs as slave unit (Mode “L-MCB”) n Mains failure detection with mains decoupling via GLS or LS-5 (MCB) n Auto mains failure operation (AMF)
GCB/GGB/L-MCB GCB/GGB/L-MCB control (open/close) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n GCB operation (relay output to close GCB) n GGB operation (relay output to open and close the GGB) n MCB operation via LS-5, LS-5 runs as slave unit (Mode “L-MCB”) n Mains failure detection with mains decoupling via GLS or LS-5 (MCB) n Auto mains failure operation (AMF)
GCB/L-GGB/L-MCB GCB/L-GGB/L-MCB control (open/close) This application mode provides the following functions: n Measuring of engine/generator parameters (i.e. voltage, frequency, current, power, coolant temperature, oil pressure, etc.) n Engine start/stop n Engine/generator protection (relay output to open GCB) n GCB operation (relay output to close GCB) n GGB operation via LS-5, LS-5 runs as slave unit (Mode “L-GGB”) n MCB operation via LS-5, LS-5 runs as slave unit (Mode “L-MCB”) n Mains failure detection with mains decoupling via GLS or LS-5 (MCB) n Auto mains failure operation (AMF)
Operation Modes
The easYgen-3000XT offers four operation modes:
n AUTO n MANUAL (MAN)
n TEST n STOP
n ... and an internal (non) operating phase during starting the device itself
The plastic housing (HMI) version of the easYgen-3000XT enables to select an operation mode by pressing the according button at the front panel - if current settings allow this function.
_1nYLL8.png)