F 8650X (0606)
For the serial interface only the bus station no. 1-31 can be set.
Within an Ethernet network the bus station no. can be set from 1 to 99. Therefore the switches
S1-6/7 must be set in addition to the switches S1-1/2/3/4/5.
The number of the communication partners within a network is still limited to 64.
This enhanced setting of the bus station no. is only possible from operating system BS41q/51q
V7.0-8 (05.31) of the central module.
Processor module X-CPU 01 For high performance requirements and large safety applications, 4 x RJ-45
Processor module X-CPU 31 For smaller and mid-size safety applications, 4 x RJ-45
System bus module X-SB 01
Communication module X-COM 01 4 x RJ-45, 2 x 9-pole D-Sub, up to 6 different protocols
Inputoutput modules Type Description
Input modules
Digital input module X-DI 64 01 64 channels, 24 VDC, SIL 3
Digital input module X-DI 64 51 64 channels, 24 VDC
Digital input module X-DI 32 01 32 channels, 24 VDC, SIL 3

Applications with the communication module F 8627X:
– connection of the central module to a PADT (ELOP II TCP)
– connection to other communication partners within an Ethernet network (safeethernet,
Modbus TCP)
The communication runs from the central module via the backplane bus to the communication
module F 8627X and from the Ethernet ports of the F 8627X into the Ethernet network and vice
versa.
Special features of the central module:
– Self-education: from operating system BS41q/51q V7.0-8 (05.31)
– ELOP II TCP: from operating system BS41q/51q V7.0-8 (05.31)
Further informations about the bus station no., ELOP II TCP, loading of operating systems and
application programs (self-education) et al. corresponding to the central module you will find in
the data sheet of the F8627X as well as the operating system manual of H41q/H51q and the
safety manual of H41q/H51q.
Before removing a central module its fixing screws must be completely
loosened and freely movable. Remove the module from the bus board
by pushing the ejection lever (front label) top down and quickly removing
in an upward motion to ensure that faulty signals are not triggered
within the system!
To attach the module, place it on the terminal block and press it
inwards as far as it will go. This action should be performed quickly to
ensure that faulty signals are not triggered within the system!
Diagnostic display of the central module
– Four digit alphanumerical display,
– two LEDs for the general display of errors (CPU for the central modules, IO for the testable
input/output modules),
– two toggle switches to request detailed error information,
– push-button ACK resets the error indication;
in failure stop ACK behaves like restarting the system.
For further information on the diagnostic display and lists of error codes, refer to the documentation
"Functions of the operational system BS 41q/51q" (also on ELOP II CD).
Notes for start-up and maintenance
– Lifetime of the buffer battery (without voltage feeding):
1000 days at TA = 25 °C
200 days at TA = 60 °C
– It is recommended to change the buffer battery (CPU in operation) at the latest after 6
years, or with display BATI within three months
(Lithium battery, e.g. type CR 2477N, HIMA part no. 44 0000018)
– Check the bus station no. and transmission rate at switch S1 for correct settings
– Important: When upgrading an F 8650 to an F 8650X module the fan concept has also to
be changed!