The module is automatically tested during operation. The main test routines
are:
– Reading back of the output signals. The operating point of the 0 signal
read back is ≤ 6.5 V. Up to this value, the level of the 0 signal may arise
in case of a fault, and this will not be detected
– Switching capability of test signal and cross-talking (walking-bit test).
Outputs 500 mA, k short circuit proof
Internal voltage drop max. 2 V at 500 mA load
Admissible line resistance (in + out) max. 11 Ohm
Undervoltage tripping at ≤ 16 V
Operating point for
short circuit current 0.75 ... 1.5 A
Outp. leakage current max. 350 µA
Output voltage if output is reset max. 1,5 V
Duration of the test signal max. 200 µs
Space requirement 4 TE
Operating data 5 V DC: 110 mA
24 V DC: 180 mA in add. load

Planning hints– max. 10 output modules with nominal load may be used in one I/O
rack
– can be paralleled without external diodes
– for lamp load 4 W to 10 W refer to sketch: