Fisher LCP100 Local Control Panel
Source: | Author:kongjiang | Published time: 2024-12-04 | 9 Views | 🔊 Click to read aloud ❚❚ ▶ | Share:
Fisher™ LCP100 Local Control Panel
Fisher™ LCP100 Local Control Panel
Introduction
Scope of Manual
Description
The LCP100 local control panel is used with the HART? communicating DVC6200 SIS digital valve controller. This panel is used to manually open and close a safety shutdown valve. The LCP100 also provides a manual reset feature as well as a button for initiating a partial stroke test.
Specifications
Specifications
Typical specifications for the LCP100 local control panel are shown in Table 1.
Instruction Manual
Specifications
Power Options (switch selectable)
External: 24 VDC +/- 10% @ 50 mA maximum continuous current (100 mA maximum inrush)
Loop: 8‐20 mA (LCP100 and DVC6200 SIS combined)
Power Consumption
External: 1.32 W max continuous
Loop (Point-to-Point): 0.042 W max continuous
Loop (Multi-Drop): 0.126 W max continuous
Temperature Limits(1)
-40 to 65? C (-40 to 149F)
Maximum distance between LCP100 and DVC6200 SIS digital valve controller
Cable length is limited by maximum cable capacitance of 100,000 pF(2). Typical 314 meters (1030 feet) with 18 AWG shielded Audio, Control and Instrumentation Cable.
Electrical Classification
CSA (C/US)
AEx ia IIB T4 Ga(3) – Zone 0, 1, 2
AEx e mb [ib] IIC T4 Gb – Zone 1, 2
AEx ic IIC T4 Gc – Zone 2
Class I Division 2 Groups ABCD T4
ATEX
Ex ia IIB T4 Ga(3) – Zone 0, 1, 2
Ex e mb [ib] IIC T4 Gb – Zone 1, 2
Ex ic IIC T4 Gc – Zone 2
IECEx
Ex ia IIB T4 Ga(3) – Zone 0, 1, 2
Ex e mb [ib] IIC T4 Gb – Zone 1, 2
Ex ic IIC T4 Gc – Zone 2
Ex tb IIIC T71°C Db – Zone 21, 22
Other Classifications / Certifications CUTR— Customs Union Technical Reg
CUTR— Customs Union Technical Regulations (Russia, Kazakhstan, Belarus, Armenia)
ESMA— Emirates Authority for Standardization and
Metrology - ECAS-Ex (UAE)
Installation
WARNING:
Electrostatic charge hazard. Do not rub or clean the LCP100 with solvents if a flammable vapor is present. To do so could
result in an explosion.
Note

Direct all wiring to the left side inside the LCP100 compartment, away from the buttons.