Eaton Magnum SB Series – Low Voltage Insulated-Case Power Circuit Breakers
Source: | Author:kongjiang | Published time: 2026-07-16 | 43 Views | 🔊 Click to read aloud ❚❚ ▶ | Share:
Eaton Magnum SB Series – Low Voltage Insulated-Case Power Circuit Breakers

Application Flexibility and Reliable Performance

Eaton’s Magnum™ SB is a low-voltage insulated-case power circuit breaker family engineered specifically for the performance and economic requirements of UL® 891 switchboards. Listed under UL 1066, the Magnum SB delivers the robustness of a power circuit breaker with the compact footprint and economics of a molded-case solution, making it an ideal choice for demanding switchboard applications.
All Magnum SB breakers feature a fixed instantaneous trip of 18×In18×I

, ensuring fault clearing within three cycles to meet switchboard class requirements. Their short-time withstand and interruption ratings are optimized for 480 Vac systems, providing dependable protection where it matters most.

Key Features & Benefits

  • Switchboard Class Design – Purpose-built for UL 891 switchboards with fixed instantaneous trip settings characteristic of UL 489 molded-case breakers used in these applications.

  • Broad Performance Range – Available from 200A to 6000A continuous current with interrupting ratings from 50 kA to 150 kA and short-time withstand up to 100 kA.

  • 100% Rated – Full continuous current rating across all frame sizes without derating.

  • Three Frame Sizes – Narrow, Standard, and Double frames to facilitate compact enclosure configurations and optimize panel space.

  • High Withstand Options – Maximize system coordination with breakers offering superior short-time withstand capabilities.

  • Current Limiting Models – Fuseless fast-opening Magnum SB breakers deliver high interrupting ratings with low energy let-through, significantly reducing arc flash hazards.

  • Field-Installable Accessories – UL-approved accessories common across all Magnum breakers, easily added or replaced at the point of use without factory recalibration.

Digitrip™ Trip Unit Family – Protection, Coordination & Diagnostics

All Magnum SB breakers are equipped with microprocessor-based Digitrip™ RMS trip units, offering scalable functionality from basic overcurrent protection to advanced power monitoring:
  • Programmable overcurrent protection and alarms

  • Ampere and power metering with power quality analysis

  • Local display for real-time information and diagnostics

  • Communication via translators to standard protocols: Modbus, INCOM™, and PROFIBUS®

  • Zone-selective interlocking for improved coordination

  • Arcflash Reduction Maintenance System™ technologies for arc flash mitigation

  • Breaker health monitoring for predictive maintenance

Safety & Certifications

  • ANSI, UL, CSA®, and NEMA® certifications and approvals

  • Arc flash reduction solutions integrated into the design

  • Closed-door levering and controlled access for enhanced operator safety

  • Primary disconnecting contacts are mounted on the breaker for ease of inspection and replacement.

Complete Model Lineup – Magnum SB Series

Breaker TypeFrame TypeFrame AmperesInterrupting Ratings (kA) at 508 VacShort-Time Withstand (kA)
SBN-508Narrow8005020
SBN-608Narrow8006520
SBN-C08Narrow80010020
SBS-608Standard8006520
SBS-C08Standard80010020
SBN-512Narrow12005025
SBN-612Narrow12006525
SBS-C12Narrow120010025
SBS-612Standard12006525

All models are available in three- and four-pole configurations, with fixed or drawout mounting options, and support a wide range of current sensor and rating plugs to establish the breaker In rating (200A – 6000A).

Maintenance, Modification & Service

  • UL-approved field-installable accessories common across all frame sizes

  • Primary disconnecting contacts are mounted on the breaker for easy inspection and replacement

  • Renewal parts readily available for point-of-use service

  • Eaton Electrical Services & Systems available for startup and ongoing support